CHG-IOM-001 MAR-06
Installation and Maintenance ManualWiring Diagrams
This manual to is to aid the qualified HVAC contractor in the Installation and Maintenance of this Quietside R410a Ductless Mini SplitPlease read and
Installer Supplied ItemsRefrigerant Line Set : Flare Connection only, suitable for R410A with both lines insulated, max length 45ftMain System Breaker
Controls and ComponentsUnits are supplied with a wireless remote controller, which communicates with the unit Microprocessor controllerThe return air
Step3Drill Hole for Line Set etcRemove mounting bracket from the rear of the Indoor unit, use a Phillips head screwdriver to remove the unit pipe stra
Step 6Install unit on Mounting BracketFeed the line set stubs/condensate hose/wiring connections through the ø 3" hole, then locate the unit key
Step 9EvacuationGauges can now be attached to the service ports - SERVICE PORTS HAVE A 5/16" CONNECTION TO GAUGES, WHICH IS DIFFERENT TO THE NORM
Step 11Controls WiringElectrical Wiring should be done in accordance with all National ElectricalCode (NEC) and local state/city building codesALL CON
With the refrigerant system completely evacuated the system can now be opened to allow the refrigerant charge in the Outdoor unit to be released into