*FJM (MH) Model Series Systems Manual Addressing
Step 1
• Manual addressing is used when a BMS system is used or Ducted and Wall Mount units have Wired
Remote controls
• Set the rotary switch to the number of units, either 2, 3 or 4
Step 2
• Manual Addressing
• *Set Dip Switch #1 on Outdoor unit to OFF
Step 3
• On Indoor units set SW02 the MAIN address to the following based on which set of refrigerant
connections the unit is piped to
• Unit piped to the top set of connections = 0
• Unit piped to the second set of connections from top = 1
• Unit piped to the third set of connections from top = 2
• Unit Piped to the lowest set of connections = 3
• System can now be powered up
Step 4
• On initial power up LH display will scroll 00 Through 15
• Once Indoor units are tracked LH display will show 00, 01, 02 and 03 depending how many Indoor
units are installed
Step 5
• Use the K2 Button to put the unit into either Cooling or Heating trial mode
• Press K2 Button ONCE for Heating Trial mode : Display will show |-1
• Press K2 Button TWICE to add refrigerant : Display will now show |-2
• Press K2 Button THREE times for Cooling trial mode : Display will now show |-3
• Press K2 Button FOUR times for Pump Down mode : Display will now show |-4
* Dip Switch #1 should be in the OFF position (MANDATORY on the FECA Ducted unit)