*FJM (MH) Model Series Systems Manual Addressing
Step 1
Manual addressing is used when a BMS system is used or Ducted and Wall Mount units have Wired
Remote controls
Set the rotary switch to the number of units, either 2, 3 or 4
Step 2
Manual Addressing
*Set Dip Switch #1 on Outdoor unit to OFF
Step 3
On Indoor units set SW02 the MAIN address to the following based on which set of refrigerant
connections the unit is piped to
Unit piped to the top set of connections = 0
Unit piped to the second set of connections from top = 1
Unit piped to the third set of connections from top = 2
Unit Piped to the lowest set of connections = 3
System can now be powered up
Step 4
On initial power up LH display will scroll 00 Through 15
Once Indoor units are tracked LH display will show 00, 01, 02 and 03 depending how many Indoor
units are installed
Step 5
Use the K2 Button to put the unit into either Cooling or Heating trial mode
Press K2 Button ONCE for Heating Trial mode : Display will show |-1
Press K2 Button TWICE to add refrigerant : Display will now show |-2
Press K2 Button THREE times for Cooling trial mode : Display will now show |-3
Press K2 Button FOUR times for Pump Down mode : Display will now show |-4
* Dip Switch #1 should be in the OFF position (MANDATORY on the FECA Ducted unit)