Specific requirements for installation in Massachusetts
In the Commonwealth of Massachusetts these units must be installed by a
licensed gas fitter or plumber
Venting :
For the Quietside models DPW-099A, DPW-120A where the bottom of the vent
termination and combustion air intake is installed at a height BELOW 4 ft above
the grade level the following requirements must be satisfied
1. If there is not one presently installed, on each floor level where there is a
bedroom(s), a Carbon Monoxide detector and alarm shall be installed in
the living area outside the bedroom(s). The Carbon Monoxide detector
shall comply with NFPA 720 (2005 Edition)
2. A Carbon Monoxide detector shall be installed in the room where the
ODW unit is installed, the detector shall be :
a) Powered from the same power circuit that provides power for the ODW
unit. A single electrical service switch shall be used to service both the
unit and the detector
b) Have battery back up power
c) Meet ANSI/UL std 2034 and comply with NFPA 720 (2005 Edition)
d) Approved and listed by a NRTL recognized under 527 CMR
3. A Quietside approved vent termination must be used. Installation of the
vent terminal must be in strict compliance with Quietside’s written
instructions, and a copy of these instructions must remain with the unit
after the installation is completed.
4. A metal or plastic identification plate shall be mounted on the exterior of
the building, 4ft above the vent termination. The plate shall read “Gas
Vent Directly Below” with text size visible from a minimum of 8ft.