EH035CAV Slim Duct Heat Pump Mini Split
Indoor Unit : EH035CAV Wired Remote : MWR-TH01 Outdoor Unit : UH035CAV
Power
Power Voltage :
208/230V 1 Ph 60 Hz
Control Voltage :
DDC Fuzzy Logic
Main Breaker Size :
20 A
Line Sizes :
“Liquid” (expanded gas) line
1/4
Suction
3/8”
BOTH LINES MUST BE INSULATED SEPARATELY
Interconnect Length
Maximum / Minimum Length
65 / 10 feet
Vertical lift
23 feet
(Note condenser can be above or below evaporator)
Charging
Unit is charged for
50ft (Factory Charge 35.3oz R410A)
Additional Charge of R410A
Add 0.15oz/ft when line set exceeds 50ft
Charge for Line Run lengths
Length
25
30
35
40
45
50
55
60
65
Added Charge (oz)
0
0
0
0
0
0
0.75
1.5
2.25
Interconnecting Wiring
Gauge
14 AWG Power & 16 AWG Shielded Communication
Number of Interconnecting Wires
3x14 AWG Power & 2x16 AWG Comms = 5 Total
Between unit and Wired RMC
4x16 AWG Control, 2 for 12V DC Power, 2 Comms
Indoor Unit Outdoor Unit
(Ground) F2 F2 Separate all Power
F1 F1 & Communications
Wiring by 2"
G G
2(N) 2(N)
1(L) 1(L)
L Power Supply is 208/230V
F4 N even though L & N is used
F3 for Terminal designation
V2
V1 208/230V
System
Breaker
Wired Remote
Controller
V2
F3
F4
V1