Basic Installation Tips
Sizing
Computer/Data Rooms : Basic sizing is 200-250 sqft per 12,000
Btu/h
Commercial/Retail : Basic sizing is 400-450 sqft per 12,000 Btu/h
Residential : Basic sizing is 550-600 sqft per 12,000 Btu/h
Low Ambient Cooling
Computer/Data Rooms and Commercial: As standard these units have low
ambient cooling capability down to 14 DegF outdoor temperature.
THESE UNITS CANNOT OPERATE IN COOLING BELOW 14 DEG F
AMBIENT TEMPERATURE, UNLESS EQUIPPED WITH AN APPROVED
WIND BAFFLE TO PROTECT THE OUTDOOR UNIT, IN WHICH CASE
PERFORMANCE CAN BE EXPECTED DOWN TO 0 DEG F OUTDOOR
TEMPERATURE. ALTHOUGH IF A PROLONGED OFF CYCLE IS
EXPERIENCED, THE UNIT MAY NOT RESTART.
R410A Refrigerant
Higher pressures (close to double) than R22, but the operating temperatures
are very similar to those with R22, for example
R410A A saturated suction temp of 45 DegF = Suction Pressure of 130
Psig R22 A saturated suction temp of 45 DegF = Suction
Pressure of 76 Psig
R410A uses a POE oil compared to the mineral oil used with R22, the POE oil
is attractive to water so it is very important to :
Minimize the time that the system is open to the atmosphere
Ensure that a deep vacuum is pulled on the system, 200 microns or less
Do not install any sight glasses or filter driers in the line set.
Note: It is not necessary to remove refrigerant for line sets shorter than
the specified length of the factory charge.