Pump Curves – DPW Units
The DPW units include a pump assembly that is used to provide the flow through
the unit heat exchangers, and has a nominal flow of heating water for external
piping arrangements.
This pump is not designed to be the system pump providing flow to radiant loops
or baseboard.
Therefore Quietside insists on using a Primary – Secondary pumping
arrangement, the recommended method uses the traditional large diameter
Primary loop
The main circulation pump or the zone pumps will then provide circulation into
the zones or the heating system
The only exception to this Primary – Secondary rule is for Air Handling units with
a hot water coil where the Air Handling unit is located less than 10ft from the
DPW unit.